Performa – SoP 002: Action taken report for safety 
measures complied for the accidents occurred
Sr Circle Location of Accident and details of the victim Date of occurrence Type of Accident Cause of Accident Findings of CEI / EI / AEI Remedies suggested by CEI /EI / AEI in various cases Whether the remedy suggested is complied Action taken to avoid recurrence of such Accident
  1 2 3 4 5 6 7 8 9
1 RJC Kumari Divyaben Jagdishbhai Sirsiya-rajkot 15-10-08 FHO Service Wire insulation broke at the entrance of the house due to renovation of main entry door, which was completely made of iron. The consumer has passed the service wire at the top of this door.  At that time of the accident service wire got pressed, s awaited awaited Earthing reactivated extensive preventive maintenance
2 RJC Cow of Shri Sureshbhai Vashrambhai Chavadiya-Rajkot 29/11/2008 FA Cow came into contact with live girdre pole having leakage current of street light Phase already touching the same pole. awaited awaited N.A. awareness
3 RJC Hemantbhai Manilal parmar         29/12/2008 NFHO Leakage of current from "Langaria" chrged to Amplifier of cable operator. awaited awaited N.A. Matter is emphasized to employee by sec.head.
4 RJC Hetalben Karshanbhai  29/12/2008 NFHO Leakage of current from "Langaria" chrged to Amplifier of cable operator. awaited awaited N.A. Matter is emphasized to employee by sec.head.
5 RJC Shri Ajaysinh Ashoksigh Vala 04/01/2009 NFHO The victim was climbed on Transformer Center on 11 KV side bushing,trying to take kite pulling with thread at that time R-phase Bushing Jumper was shorted with B-phase Jumper and flashover with blasting of 11 KV D.O. Fuse was occurred.Thus victim was elec awaited awaited N.A. awareness
6 RJC Shri Bhimabhai Bapubhai Parmar 06/02/2009 NFHO The construction of Silver Apartment of four storied. The victim was removing lift structure which was fixed for construction.During dismantling of temporary  lift structure the metal part of lift is came in contact with 11 KV LINE ( PARIMAL FEEDER ) acco awaited awaited rectified publishment of consumer awareness
7 RJC Shri Vikramshin Vakhatshin Baraiya 10/02/2009 NFHO While Painting the girder pole of L.T. Line, Victim was came in induction zone of 11Kv Lohanagar feeder which was crossing over the girder pole of L.T. Line on which victim was doing the painting work. awaited awaited N.A. awareness
8 RJC Shri Babubhai Bhemabhai Patel 24/02/2009 NFHO There was shut down of 11KV Doordarshan Feeder on dt. 24-02-09 from 07:40 AM and maintainance work arranged in this feeder. The maintainance area was isolated by operating gang switch from main line and line discharged through earthing rod. But some how p awaited awaited N.A. awareness
9 RJC Bharatsinh Shankarsinh Khant 01/03/2009 FHO Shut down of 66 KV Laxminagar s/s was arranged by GETCO on dtd 01.03.09. During this 66 KV S/s shut down, pole painting work was arranged by HT-2 Sub-Division by taking LC No. 15456 dated 01.03.09 on 11 kV Panchvati feeder & discharge the 11 kV line. Whil awaited awaited N A N A
1 RJR Buffalo of Batukbhai Nanjibhai Vora 05.09.08 FA Leakage current through Pole earthing Not received      
2 RJR Buffalo of Sh. Ramjibhai Popatbhai Valani at vilage: Navi-Sankli 2-Oct-08 FA The tree branch was touching to the LT line of village T/C loc no. DT-016 located near school. Due to this unbalance leakage current was passing through the neutral earth of T/C. On Dtd. 02.10.08 at about 14:30 PM, a buffalo of Sh. Ramjibhai Popatbhai whi Not received      
3 RJR Bullock of Sh. Mangalsang Chanubha Jadeja at village: Charel 4-Oct-08 FA Due to rain and wind pressure LT line conductor was broken from the joint and fallen on the earth. Hence leakage current was passing through live broken conductor. A bullock of Sh. Mangalsang Chanubha Jedeja while passing near this LT line came in contact Not received      
4 RJR   7-Oct-08 FA   Not received      
5 RJR SH.CHHAGANBHAI POPATBHAI KAKADIYA 8-Oct-08 FA ONE PHASE LT CONDUCTOR OF 3 PHASE 4 W LT LINE BROKEN NEAR POPAT GOVINDBHAI "S AG CONN & BUFFALOW CAME IN CONTACTWITH THIS COND.& GOT ELECTROCULATED & DIED. Not received      
6 RJR MANOJBHAI RAGHAVBHAI SORATHIYA 8-Oct-08 FHO As per Party's statement accident occurs due to sevice fault of 3-phase ag connection but no any evidence  found as 3-phase service wire is "ok". Not received      
7 RJR Sh. Y.G. Gohil (Helper) 14-Oct-08 NFHD For attending the 1- Q R/L Service Fault of Consumer Victim was working on the P.S.C Pole and at the time of working, Victim touch   the phase conductor of L.T. Line and due to the jerks Victim unbalanced and fell down. Not received      
8 RJR Sh. Anil Chetan at village: Boriya 16-Oct-08 NFHO Sparking was occurred due to loose 11 KV line jumper & hence 11 KV line conductor was broken from the load side jumper binding and fallen on the ground. Hence return leakage current was flowing through the broken conductor. A 10 years child while passing  Not received      
9 RJR Smt. Chanduben Chetan at village: Boriya 16-Oct-08 NFHO Sparking was occurred due to loose 11 KV line jumper & hence 11 KV line conductor was broken from the load side jumper binding and fallen on the ground. Hence return leakage current was flowing through the broken conductor. A 10 years child while passing  Not received      
10 RJR Sh. Dhirubhai Chhaganbhai Makadiya (Helper) at village Bhayavadar 12-Nov-08 FHD As per Complain of AG Farmar Shri Navinbhai Bachubhai Makadiya at village Bhayavadar for breakdown of power supply, victim Shri Dhirubhai Chhaganbhai Makadiya(Helper)was gone at site to attend fault and observe lug & jumper fault on TC. While attending ju Not received      
11 RJR BUFFALO OF SH.NARAN AMBARAM 26-Nov-08 FA SNAPING OF LT LINE CONDUCTOR BUFFALOW CAME IN CONTACT WITH THIS BROKEN CONDUCTOR Not received      
12 RJR Mignesh N. Pachani 28-Dec-08 FHO FROM  VICTIM 'S FATHER(SHRI NAROTAMBHAI TRIKAMBHAI PANCHANI) STATEMENTAND SITE CONDITION IT CAN BE CONCLUDE THAT AS WHEN  VICTIM TRY TO SWITCH ON "VALONU " (ELECTRIC MACHINE FOR PREPARATION OF BUTTER MILK) IN HIS OWN PRIMISES, DUE TO UNPROPER FIXING OF PL Not received      
13 RJR Jasminben Gulambhai Sipai 28-Dec-08 NFHO Leakage Current Through Earthing of Pole. Not received      
14 RJR Ramesh Harjibhai Jivani 4-Jan-09 NFHO Victim shri Rameshbhai Harjibhai Jivani (Vij Ghar Helper) while giving LT cable connection on the LT side of T/C came in contact with the middle phase D O fuse contact where approximately 8 c.m. fuse wire found hanging and electric shock resulted him to f Not received      
15 RJR Dhaval Bharatbhai Parmar 14-Jan-09 FHO Due to Kite festival victim try to catch the kite from tree
but by mistake he touched the 11 k.v. line and met accident.
Not received      
16 RJR Cow 26-Jan-09 FA Due to heavy wind pressure on dt. 26.01.2009 conductor of 11 KV Navlakhi feeder snapped on cow passing under the 11 KV line and due to return current flowing in conductor in load side cow met with an electrical accident Not received      
17 RJR Smt. Bhavnaben Pankajjati Goswami  28-Jan-09 FHO While making the investigation in detail it is found that victim was fetching the water by connecting a motor pipe to the Nagarpalika water supply pipe at about 13:30 hours. The body of the water pump's motor was short. She came out from his house and came in contact with short circuited motor body and got an electric shock. Thus occurred a human being fatal accident at private premises.   Not received      
18 RJR Sh. Ashoksinh Fatehsinh Parmar  14-Feb-09 NFHD To release 3 Ph. C/L connection of Sh. Jabar Govind at village Dumiyani & after removing D.O. fuse of T/C when victim climbed on pole a fire flies (Agia) stuck on his right hand & he loose his balance & fall down on ground from the pole and he got fracture on his left leg.     Not received      
19 RJR PRAKASH PARSHOTAMBHAI CHUDASAMA 24-Feb-09 NFHD On date 27-2-09 at around 4:00 PM Victim Sh Prakash P. Chudasama, while climbing
the LT line Pole to attend disconnection of 1 Ph temporary connection of Indus
Tower-Navagam and as he  reached to second slot of PSC pole from top end, due to biting of insect, victim lost his balance and fell down down from the pole. He was
admittedto Hospital of Dr Sh Dipak R. Langalia . He had injury (fracture) on both
hand   wrists. Thus mechanical non fatal accident occurred to victim.
 
Not received      
20 RJR Lilaben Vithalbhai Pipaliya 01.03.09 FHO An accident occurs, due to short ckt in Motor of Consumer (In consumer premises) Not received      
21 RJR H. K. Detroja 5-Mar-09 NFHD Sh. H. K. Detroja was working on LT line, on Tower Ladder Vehicle to attend consumer Complaint of Consumer Sh. Prakash Dhanjibhai Kanjariya, Consumer no. 84304/07646/9 vide complain no. 21684 dt. 05/03/2009 time 15:00. During his work he accidentally touched to live Conductor & hence got momentary electrical jerk. Due to this he lost his balance on ladder and fall down & got Non Fatal Accident. He got fracture in his left Hand. He was immediately shifted to Prabhat Hospital, Near Old S.T. Stand, Morbi for necessary medical treatment Not received      
22 RJR SH.maganbhai Kadvabhai Bhenderi 15-Mar-09 FA Gaurding of lt line touched with one phase of 3-ph 4-w line and it touched with LT angle and earth wire ,leakage current passed through earth wire.bullock came in contact with earth wire and got electric shocked and died. Not received      
23 RJR Shabbir Husenbhai Sumra 17-Mar-09 FHO While going through primary investigation after information of above accident, it was noted that victim’s parents has not informed to P.G.V.C.L. and they have not informed to Local Police regarding accident. Hence, police complaint of above accident is not logged. While asking to local peoples they have said that accident was occurred approximately between 3:00 pm to 4:00 pm on dt. 17.03.2009. but it was noted that between 3:00 pm to 4:00 pm there was not any tripping on 11 KV Hajnali JGY Feeder. Also there is no any clear Eye Victim of Accident. Hence it is difficult to find factual report of accident. How ever at the time of site visit & investigation it was noted that there were few spots on Neem tree’s branch where the accident was occurred. So, as per statements of local peoples it may possible that while playing on tree accidentally victim’s body came in induction zone of 11 kv Hajnali Feeder and he may got electric shock. After that local peoples have given first aid (primary treatment) to the victim until arrival of ambulance. Then they went to Mangalam Hospital, Morbi where doctor on duty has declared that victim is no more. After that Doctor suggested them to referrer to Civil Hospital Morbi for Post Mortem. But victim’s parents have not referred to Civil Hospital Morbi instead they went back to their village Biliya & made burial of corpse. So, post mortem report is also un available. Hence from all above findings/ happening the exact reason of accident can not be determined perfectly. Investigation of Electrical Inspector is pending Not received      
24 RJR Mitesh Kantibhai Kakkad 30-Mar-09 NFHD On Dt. 30.03.2009 Shri Mitesh Kantibhai Kakkad, ALM ,PGVCL, TANKARA was charging new Transformer for New AG SPA Connection of Ag Applicant Sh. Naresh Amba at Village Kalyanpar Ta. Tankara. While giving 11 KV Line Jumper on Hanumangadh Ag Feeder connections on the Top side of Transformer D O Fuse from Tapping to T/C., Sh. Miteshbhai Suddenly got shock resulted him to fall down on the ground and met with Non Fatal accident.
Line Clear of Feeder was taken by him before starting the work vide L/C no. 23560 Dt. 30.03.09 at 17:15. He was working on line with wearing helmet. He was working on line after earthing One Phase of Line with Earthing Road. Sh. Ketan Sardhara, Apprentice Line man was also there with sh. Mitesh bhai but he was standing at ground level.
As per preliminary investigation, it may possible that due to crossing of 66 KV Line Induction current flown or Back Power of Near By LT Line flown through near by AG T/C in line & sh. Miteshbhai got electrical jerk. At the time of accident there was not any tripping on any near by feeders so it is possible that power was not flown through any 11 KV Feeder.
Sh. Miteshbhai had got minor injury as he had wearied helmet & due to this his life was saved & not get severe injury in his head. He was getting little pain in his hand & waist & not having any fracture in his body. Detail Investigation Report is Avaited
Not received      
1 PBR Fatal accident to -  Human Outsider -   Niranjan Vallabhdas Gondaliya, Age approx 17 years at Village: Keshod under Keshod-Town S/Dn. 17/10/2008 FHO Victim might been accidently touched with the live wire of 11 KV line of 11 KV line, while passing through on open gallery at 3rd floor of JD complex, resulted in to fatal accident to victim. CEI /EI/Dy CEI Report Awaited - - N.A.
2 PBR Fatal accident to -  Human Outsider -   Hasinaben Valibhai, Age approx 28 years at Village: Keshod under Keshod-Town S/Dn. 20/10/2008 FHO Victim came in contact with live phase wire, while inserting defective pin of Electric motor in to plug with wet hand in his private premises resulted in to fatal Accident to her. Due to defective Swith Board in her private premises, victim came contact with it and live wire resulted in to Fatal accident to her. N.A. N.A. N.A.
3 PBR Fatal accident to -  Human Outsider -   Malde Kandha Parmar, Age approx 40 years at Village: Gorsar under Madhavpur S/Dn. 17/10/2008 FHO There was no Eye Witness. As per the statement of relatives of victim, victim met with an electrical accident, While Switch "ON" the defective electrical motor of Agriculture in his Farm i.e. Private Premises.  There was no any fault from PGVCL side, victim met with an accident due to other reason. N.A. N.A. N.A.
4 PBR Fatal accident to -  Human Outsider -   Shri Dineshbhai Rambhai Bhuva, Age approx 18 years at Village: Balej under Madhavpur S/Dn. 31.10.08 FHO Victim met with an electrical accident & electrocuted, While Switch "ON" the defective electrical motor of Grinder of Quary in Private Premises.  Victim came in contact with defective motor of grinder in his PVT premises. It might be avoided if owner of quary has provided ELCB of  propoer capacity in his installation.  N.A. N.A. N.A.
5 PBR Fatal  accident to -  Human Outsider -   Shri  Bharatbhai Bhayabhai Sadiya, Age approx 22 years (approx) years at Village: Bagvadar under Bagvadar S/Dn. 10/01/2009 FHO Victim came in contact with live HT wire of 11 KV Bagvadar JGY feeder while civil work is being carried out on the top of building by him as the same is constructed under existing 11 KV line, resulted in to fatal accident to him. CEI /EI/Dy CEI Report Awaited - - N.A.
6 PBR Fatal  accident to -  Animal  -  Cow of Smt. Vijayaben Hansrajbhai Hingrajiya,   at Village: Ajab under Keshod-R-1 S/Dn. 17/02/2009 FA Fault occurred in 1-phase Service wire at LT Pole end, Grass under the service line burnt out due to sparking, Cow was there & met with fire accident. CEI /EI/Dy CEI Report Awaited - - N.A.
7 PBR Fatal  accident to -  Human Departmental - App. Line Man  Shri Lakhman Punja Kodiyatar, Age approx 28 years at Village: Mangrol under Mangrol Town S/Dn. 24/02/2009 FHD To carry out the work for replacement of LT Cable, "Coronation Highschool vali" 11 KV AB Gang Switch to be isolate but by mistake Shri H M Jaga - Asst. Line man has isolated 11 KV AB Switch of another Section i.e. "Kagrana Vali". Shri Lakhman Punja Kodiya CEI /EI/Dy CEI Report Awaited - - Disciplinary action initiated against defaulter Asst Line Man Shri Jaga and he is immediately suspended.
1 JMN A Buffalo 07.10.08 FA Conductor of 11 kv line was snapped while passing the buffalo it came in contact with live wire and it got shocked. Awaited Awaited    
2 JMN A Buffalo 07.10.08 FA Conductor of 11 kv line was snapped while passing the buffalo it came in contact with live wire and it got shocked. Awaited Awaited    
3 JMN Smt. Gulshan ben Yusufbhai Ahmed 08.10.08 FHO Shock circuited in the motor of sewing machine of Victim's under her premises, comes electric shock to victim and got died. Awaited Awaited    
4 JMN Buffalo 12.10.08 FA Due to wind pressure, LT cond. Contact with each other and cond. Snapped and falldown to the buffalo and the buffaloes mad path for electricity flow to wards earth and died. Awaited Awaited    
5 JMN Buffalo 12.10.08 FA Due to wind pressure, LT cond. Contact with each other and cond. Snapped and falldown to the buffalo and the buffaloes mad path for electricity flow to wards earth and died. Awaited Awaited    
6 JMN Buffalo 12.10.08 FA Due to wind pressure, LT cond. Contact with each other and cond. Snapped and falldown to the buffalo and the buffaloes mad path for electricity flow to wards earth and died. Awaited Awaited    
7 JMN Smt. Maniben Desurbhai Chavda 28.10.08 FHO Conductor was snapped but feeder was not tripped. While passing through the field, Victim got electrolux through leg.  Awaited Awaited    
8 JMN Shri Maksudbhai Sidikbhai Garana 31.10.08 FHO While shifting of house material  to another house unplugging of DVD pin from TV, due to short circuit in DVD on TV, this accident occurred in his own premises. Awaited Awaited    
9 JMN A Buffalo 12.12.08 FA A Buffalo rubbed it's body with pole. Suddenly power supply is going through earthing wire and buffalo got electric shock. Awaited Awaited    
10 JMN Shri Gopalbhai B. Akabari 27.01.09 FHO While Victim passing through way in his Ag. Field, he came in contact of snapped LT Cond. And he got electrolux. The cond. Of LT -R phase was snapped nr. 3 ft. approx. from shackle point and only sparking found from that place where cond. Was found snapped.  Awaited Awaited    
11 JMN Shri Chhaganbhai C.Pargi 02.02.09 NFHD After removing the DO fuse prior to the location where new HT line for T/C centre is required to be charged from existing network, while giving the jumper in existing line power comes from unidentified location and due to this electric jerk, the Victim fell down from the pole and accd. occurred. Awaited Awaited    
12 JMN Shri Kasambhai Karubhai 03.02.09 NFHO Victim was laying cable for TV Disc. Connection to provide cable conn. To some one else during due course of this work cable touched the 11 kv cond. Passing over there and met with n.f. accident. Awaited Awaited    
13 JMN Shri Bhairav Mangabhai Ravat 24.02.09 FHO While unknown vehicle passed through the road, it streaches a single ph. Service line. Due to it though the service wire fixed on service angle on pole and service metal pipe on house side due to tension the service pipe fallen down & service wire also broken while Victim came in contact with pipe, he got electrolux. Awaited Awaited    
14 JMN A Buffalo 26.02.09 FA LT line cond. Was broken at the site & same time said buffalo came in contact with live cond. And got ele. Shock. Awaited Awaited    
15 JMN Shri Dipak Bhupatbhai Parmar 05.03.09 FHO There is no evidence of ele. Accident on site. There was no black spot or burning signs on 11 kv conductor, jumpers as well as on aluminium patties through which it is claimed that ele. Current passed to Victim body from line 11 kv conductor. Awaited Awaited    
16 JMN Shri Jaysukhlal H.Shah 21.03.09 NFHD while attending do fuse of T/C centre, by mistake line clear of other feeder taken also proper safety gadgets not used by victim, he claimed on t/c and got ele. Shock is cause the accident. Awaited Awaited    
1 BHJ Deshalpar (Makhana Sim)      Ibrahimbhai A. Theba    09.10.08 NFHD While carrying out maintenance work on LT pole,the victim fell from LT Pole, which broke during maint. Work. Not Yet Received  Not Yet Received  Not Yet Received  Line staff instructed accordingly & Maintanance carried out    
2 BHJ Samkhiyali(Jangi)               Kadar Ismail Nurmamad rauma 15.10.08 FHO From the villagers it has come to knowledge of D.E. Samkhiyali that The Victim came in contact with water in bucket in which electric rod was immpresed for heating water the victim got an electric shock and immidiately try to pull his hand out while doing Not Yet Received  Not Yet Received  Not Yet Received  Service line is replaced by twin core cable, Earthing is reactivated at installation    
3 BHJ Samkhiyali                  Girdharsing Gangasing Rajput 1.11.08 NFHO The vehicle driver of Trailer no. GJ 12Z 1228 was driving his vehicle under the 11KV Line of Samkhiyali JGY Fdr. Due to bumpy Road the container on the trailer came in contact with live 11KV Conductor. Thus, the driver met with non-fatal electrical accide Not Yet Received  Not Yet Received  Not Yet Received  Work under progress to raise the hieght    
4 BHJ Bhuj R (Bhuj)                                  Calf 8.11.08 FA Due to break down of conductor Not Yet Received  Not Yet Received  Not Yet Received   Maintanance carried out    
5 BHJ Madhapar(Near Saiyadpar Patiya)    Siddik Hussain Manjothi     16.11.08 FHD Mechanichal fatal accident as victim has fell down from PSC pole of 11KV Chubdak fdr. Not Yet Received  Not Yet Received  Not Yet Received  Line staff instructed accordingly    
6 BHJ Anjar Town(Anjar)               Cow  30.11.08 FA Due to heavy wind pressure and rain , leakage current might have passed through girder pole to Cow & Ox. Not Yet Received  Not Yet Received  Not Yet Received  Girder pole replce by PSC pole and New earthing is provided with insulated pipe.    
7 BHJ Anjar Town(Anjar)              Ox  30.11.08 FA Due to heavy wind pressure and rain , leakage current might have passed through girder pole to Cow & Ox. Not Yet Received  Not Yet Received  Not Yet Received  Girder pole replce by PSC pole and New earthing is provided with insulated pipe.    
8 BHJ Khavda(Sovala)                  Buffalo 2.12.08 FA Due to break down of LT conductor, Buffalo came in contact with live wire. Not Yet Received  Not Yet Received  Not Yet Received   Maintanance carried out    
9 BHJ Bhuj City 1 (Bhuj )                      Sakshiben Kiranbhai Solanki                             4.12.08 NFHO Due to illegal  construction near 11KV line, victim came in induction zone of line. Not Yet Received  Not Yet Received  Not Yet Received  Notice given to party    
10 BHJ Mandvi T(Mandvi)              Valji Mithubhali Koli 5.12.08 FHO Construction work was carried out by victim under 11kv New gate feeder. During construction work victim was work with greenly wooden stick and stick came in contact with to 11kv Live Phase of New Gate feeder. He got current through greenly wooden stick &  fatal accident occurred Not Yet Received  Not Yet Received  Not Yet Received  Notice given to party for illegal construction under 11KV line      
11 BHJ Bhuj City 1 (Bhuj )                      A. P. Bhanushali                                     11.12.08 NFHO At time taking direct unauthorized connection from transformer center distribution box, due to short circuit MCCB triped and burnt the MCCB, Victim came in contact with electrical power and fire. Not Yet Received  Not Yet Received  Not Yet Received  Lock the distribution box to avoid unauthorizeed connection.      
12 BHJ Bhimasar (Pragpar-Umiya road) Salemsing  Gulabsing Bariya,  16.12.08 NFHO The victims(Contractor person) were doing the work of  replacement of open conductor by coated conductor between Ratneshwar JGY and Umaiya ag feeder of 66KV Pragpar s/s. Due to moisture in  atmosphere  &  Crossing of 66kv line at the location of the victims Got minor shock due to  Electrical –Induction.  Not Yet Received  Not Yet Received  Not Yet Received  Notice given to contractor      
13 BHJ Bhimasar (Pragpar-Umiya road) Lallubhai Vechadbhai Bariya, 16.12.08 NFHO The victims(Contractor person) were doing the work of  replacement of open conductor by coated conductor between Ratneshwar JGY and Umaiya ag feeder of 66KV Pragpar s/s. Due to moisture in  atmosphere  &  Crossing of 66kv line at the location of the victims Got minor shock due to  Electrical –Induction.  Not Yet Received  Not Yet Received  Not Yet Received  Notice given to contractor      
14 BHJ Bhimasar (Pragpar-Umiya road) Virsang magan Bariya 16.12.08 NFHO The victims(Contractor person) were doing the work of  replacement of open conductor by coated conductor between Ratneshwar JGY and Umaiya ag feeder of 66KV Pragpar s/s. Due to moisture in  atmosphere  &  Crossing of 66kv line at the location of the victims Got minor shock due to  Electrical –Induction.  Not Yet Received  Not Yet Received  Not Yet Received  Notice given to contractor      
15 BHJ Anjar R(Kotada)                                Arat Mera Nayak 19.12.08 NFHO While put up DO fuse for replaced T/C , get electrical shock. Not Yet Received  Not Yet Received  Not Yet Received  Notice given to contractor      
16 BHJ Khavada(Servo)                                            Buffalo 5.1.09 FA Due to snapping of 11KV Conductor Not Yet Received  Not Yet Received  Not Yet Received  Maintenance carried out       
17 BHJ Khavada(Servo)                                            Buffalo 5.1.09 FA Due to snapping of 11KV Conductor Not Yet Received  Not Yet Received  Not Yet Received  Maintenance carried out       
18 BHJ Anjar City                Mohanbhai D.Chauhan       10.1.09 NFHD During Installation Checking he was standing on wooden Table, accidentally the table broke and he fell down from it and got injury in his both hands and head.(Mechanical) Not Yet Received  Not Yet Received  Not Yet Received  Line staff instructed accordingly      
19 BHJ Anjar City                         Bayaben Mamad Bayad   28.1.09 FHO Due to puncture in Service line phase wire of service touched with MS Angle. With same Angle one Steel Wire is connected for hanging the wet cloths for drying purpose. So at the time of hanging the wet cloths victim might have came in contact of steel wir Not Yet Received  Not Yet Received  Not Yet Received  New S/L with new G.I. Wire and real isulators are provided      
20 BHJ Mundra II (Moti Bhujpur)     Unknown Person 20.2.09 NFHO Height of M/c loaded on trailor is more than height of 11KV line hence m/c comes in contact with 11 KV live conductor. Cleaner came in contact with metal part of trailor and got electrocuted. Not Yet Received  Not Yet Received  Not Yet Received  Raise the height of 11KV line    
21 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
22 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
23 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
24 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
25 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
26 BHJ Anjar R (Dudhai)                    Buffalo      22.2.09 FA All 6 Buffaloes were passing nearby the LT Pole of Sakariyavadi. They might have came in direct contact with un-authorized GI wire attach to the top of company’s LT pole at one end and tree Branch lying on land at another end. Not Yet Received  Not Yet Received  Not Yet Received  GI Wire remove from the pole    
27 BHJ Rapar (Rav)                      Kantibhai Hajurbhai Khant 23.2.09 FHO Due to new road work at village Rav the ground level rises around 1.5 feet due to filling of stones peaces. The driver of Dumper, doing the above work, had lifted  the trolley of Dumper and while doing so it touched  11 KV Akal Jgy feeder crossing the road. Not Yet Received  Not Yet Received  Not Yet Received  Raise the height of 11KV line    
28 BHJ Dayapar (Ghaduli)        Buffalo 28.3.09 FA Due to heavy rubbing by buffalo , stay wire broken from the anchor-rod side and came in contact with electrode of AB switch.Stay insulator is upper side of AB switch so wire became live and accident occured. Not Yet Received  Not Yet Received  Not Yet Received  Providing new stay-set with proper spacing of stay-insulator from Upper side    
29 BHJ Dayapar (Ghaduli)        Buffalo 28.3.09 FA Due to heavy rubbing by buffalo , stay wire broken from the anchor-rod side and came in contact with electrode of AB switch.Stay insulator is upper side of AB switch so wire became live and accident occured. Not Yet Received  Not Yet Received  Not Yet Received  Providing new stay-set with proper spacing of stay-insulator from Upper side    
30 BHJ Dayapar (Ghaduli)         Buffalo 28.3.09 FA Due to heavy rubbing by buffalo , stay wire broken from the anchor-rod side and came in contact with electrode of AB switch.Stay insulator is upper side of AB switch so wire became live and accident occured. Not Yet Received  Not Yet Received  Not Yet Received  Providing new stay-set with proper spacing of stay-insulator from Upper side    
1 JND Sh.Anwarbhai Hajibhai
Motimonpari, Visavadar-2 Sub-division, Rural Division-1 Division, Junagah Circle
24/09/2008 NFHO AFTER COMPLETION OF WORK THROUGH OVER SIDE VICTIM HAD ATTEMPTED TO TIE D.O. FUSE OF T.C. BY HAND WAS ELECTROCUTED MET WITH NON FATAL ACCIDENT Awating Not Applicable Not Applicable Earthing is reactivated.
2 JND FA to Buffalo
Mohbatpara , Pranchi Sub-division, Veraval Division, Junagah Circle
12/08/2008 FA Due to leakage of current in earthing. Awating Not Applicable Not Applicable Earthing is reactivated.
3 JND Fa to Buffalo
Karsangadh, Mendarda Sub-division, Rural Division-2 Division, Junagah Circle
10/10/2008 FA Due to L.T. line broken Awating Not Applicable Not Applicable Earthing is reactivated.
4 JND MISS.AMINABEN PIRABHAI GADHIYA
Veraval, GIDC VRL Sub-division, Veraval Division, Junagah Circle
12/10/2008 FHO Due to touching of lt line while she was pulling the kite on the rufe of her house Awating Not Applicable Not Applicable Earthing is reactivated.
5 JND Fa to Buffalo
Singsar, Pranchi Sub-division, Veraval Division, Junagah Circle
06/10/2008 FA Due to LT conductor broken Awating Not Applicable Not Applicable Earthing is reactivated.
6 JND Fa toCow
Bodas, Pranchi Sub-division, Veraval Division, Junagah Circle
07/10/2008 FA Due to leakage of earthing Awating Not Applicable Not Applicable Earthing is reactivated.
7 JND Fa to Buffalo
Sirvan, Talala Sub-division, Veraval Division, Junagah Circle
06/10/2008 FA Due to  heavy rain & wind the LT conductor broken and animal might have contact with the broken conductor and the accident may occurred.   Awating Not Applicable Not Applicable Earthing is reactivated.
8 JND Fa to Buffalo
Kodidra, Talala Sub-division, Veraval Division, Junagah Circle
11/10/2008 FA Due to T/c was surrounded by mud & water and land was fully wet so when buffallo of sh. jadavbhai parmar came in contact with earthing of T/C center it might have got leakage of earthing and met with an accident Awating Not Applicable Not Applicable Earthing is reactivated.
9 JND SHRI MAGANBHAI POPATBHAI, Bilkha Sub-division, Rural Division-1 Division, Junagah Circle 22/10/2008 FHO DIRECT TOUCHING TO LIVE 11 K.V. LINE FOR THEFT OF CONDUCTOR Awating Not Applicable Not Applicable Earthing is reactivated.
10 JND B.L.Savasani ( Helper ), Shapur Sub-division, Rural Division-2 Division, Junagah Circle 07/11/2008 NFHD While working for checking of Ag. T.C. at Vill Ravni with the A.L.M. G.G.Kalola the D.O. fuse of T.C. cutted ( removed ) but due to wind the D.O. fuse wire of one D.O. came in contact with each other & at the same time Mr. Savsani who was working at T.C.  Awating Not Applicable Not Applicable Earthing is reactivated.
11 JND RAJESH MOHAN JADAV, Satellite Sub-division, City Division Division, Junagah Circle 27/10/2008 NFHO to touched the uninsulated wire of  the grass cutting machine Awating Not Applicable Not Applicable Earthing is reactivated.
12 JND FA toBaby Buffalo, GIDC JND Sub-division, City Division Division, Junagah Circle 04/11/2008 FA DUE TO SNAPPING OF GUARDING WIRE AND GUARDING WIRE IS CAME IN CONTACT WITH NUETRAL WIRE AND RETURN POWER IS EARTHED THROUGH SNAPPED GUARDING WIRE AND VICTIM IS CAME IN CONTACT WITH SNAPPED GUARDING WIRE AND RESULTED DEATH. Awating Not Applicable Not Applicable Earthing is reactivated.
13 JND FA toBaby Buffalo, GIDC JND Sub-division, City Division Division, Junagah Circle 04/11/2008 FA DUE TO SNAPPING OF GUARDING WIRE AND GUARDING WIRE IS CAME IN CONTACT WITH NUETRAL WIRE AND RETURN POWER IS EARTHED THROUGH SNAPPED GUARDING WIRE AND VICTIM IS CAME IN CONTACT WITH SNAPPED GUARDING WIRE AND RESULTED DEATH. Awating Not Applicable Not Applicable Earthing is reactivated.
14 JND BHAVIN NARENDRA TANK, Satellite Sub-division, City Division Division, Junagah Circle 19/11/2008 FHO faulty equipment of his owen premises Awating Not Applicable Not Applicable Earthing is reactivated.
15 JND SH. BHAVESH BHIKHA KAMALIYA, Pranchi Sub-division, Veraval Division, Junagah Circle 25/10/2008 NFHO Due to LT Conductor broken victim might have came with the contact to this conductor. Awating Not Applicable Not Applicable Earthing is reactivated.
16 JND FA to Baby Buffalo, Pranchi Sub-division, Veraval Division, Junagah Circle 25/10/2008 FA Due to LT conductor broken Awating Not Applicable Not Applicable Earthing is reactivated.
17 JND FA to Buffalo, Pranchi Sub-division, Veraval Division, Junagah Circle 28/10/2008 FA Due to T/C cable insulation open & touch to circuit pole GI wire. Awating Not Applicable Not Applicable Earthing is reactivated.
18 JND SH. NAZIR UMAR ALAS, Talala Sub-division, Veraval Division, Junagah Circle 13/11/2008 NFHO Due to induction zone of 11 KV Sasan feeder Bus was parked under the hanging 11 kv line and the person was touched the bus with the right leg and got earthed through left leg hence, heavy current passed through his body & met with an accident. Awating Not Applicable Not Applicable Earthing is reactivated.
19 JND FA to Nil Guy, Talala Sub-division, Veraval Division, Junagah Circle 30/11/2008 FA BROKED LT WIRE WAS LYING ON THE LAND AND NILGUY WAS TOUCHED WITH LIVE WIRE WHILE WONDERING IN THE SEARCH OF FOOD AND SHOCKED AND DIED AT ATIME Awating Not Applicable Not Applicable Earthing is reactivated.
20 JND Sh. Dinesh Somabhai Parmar (Contractor Person), Visavadar-2 Sub-division, Rural Division-1 Division, Junagah Circle 08/01/2009 NFHO Due to wrong information of feeder L.C. taken for another feeder & came in to contact with live 11 K.V. line and electrocuted resulted in to non fatal accident Awating Not Applicable Not Applicable Earthing is reactivated.
21 JND Sh. Hareshbhai Menshibhai, Junagadh(R) Sub-division, Rural Division-1 Division, Junagah Circle 22/01/2009 FHO While carry out work on hand pump in private premises , the G.I. pipe line of hand pump got touched to 11 K.V. AG Rupavati feeder & got electrocuted Awating Not Applicable Not Applicable Earthing is reactivated.
22 JND Sh. Nayanbhai Devrajbhai Desai, Junagadh(R) Sub-division, Rural Division-1 Division, Junagah Circle 22/01/2009 NFHO Awating Not Applicable Not Applicable Earthing is reactivated.
23 JND Sh. Pankajbhai Bhupatbhai, Junagadh(R) Sub-division, Rural Division-1 Division, Junagah Circle 22/01/2009 NFHO Awating Not Applicable Not Applicable Earthing is reactivated.
24 JND Sh. Jayeshbhai Bhanjibhai, Junagadh(R) Sub-division, Rural Division-1 Division, Junagah Circle 22/01/2009 NFHO Awating Not Applicable Not Applicable Earthing is reactivated.
25 JND Sh. Nayankumar Damjibhai Vadukia, Junagadh(R) Sub-division, Rural Division-1 Division, Junagah Circle 22/01/2009 NFHO Awating Not Applicable Not Applicable Earthing is reactivated.
26 JND Sh. Jamal Ali Tavani
Village: NAVA VAGHANIA, Bilkha Sub-division, Rural Division-1 Division, Junagah Circle
14/02/2009 NFHO AT THE TIME OF WORKING ON PSC POLE LOST BALANCE AND MET WITH MECHANICAL NON FATAL ACCIDENT Awating Not Applicable Not Applicable Earthing is reactivated.
27 JND Sh. Muhmad Husain Kasam Khuman, Shapur Sub-division, Rural Division-2 Division, Junagah Circle 03/02/2009 NFHO The contractor Akhtar Hussain Taza’s Labour man while he was working for the Ag L.E. VDS scheme at vill. Nandarakhi, the Vrijlal Mandan Valu Grup. The victim was dismantling the 3-ph ,4-w line & after dismantling two wire he loose his balance while he was Awating Not Applicable Not Applicable Earthing is reactivated.
28 JND Sh. Laxman N Ram, Shapur Sub-division, Rural Division-2 Division, Junagah Circle 12/02/2009 NFHD Non Fatal Accident occurred to three helpers of Shapur S/Dn. While they were working for line maintanace work (L.T.) & the L.T. wire touched with 11 K.V. JGY due to broken of Guy-Clamp which was fix with C-Clam & met with Non Fatal Accident. Awating Not Applicable Not Applicable Earthing is reactivated.
29 JND Sh. Dipak R Parikh, Shapur Sub-division, Rural Division-2 Division, Junagah Circle 12/02/2009 NFHD Awating Not Applicable Not Applicable Earthing is reactivated.
30 JND Sh. Bhavesh P Dhaturiya, Shapur Sub-division, Rural Division-2 Division, Junagah Circle 12/02/2009 NFHD Awating Not Applicable Not Applicable Earthing is reactivated.
1 BVN J.R.Nimbar 25-10-08 NFHD Mechanical accident AWAITED      
2 BVN Cow of Rana Raja Mer 04-07-08 FA Due to lekage of current from broken LT conductor AWAITED Not Applicable Not Applicable Necessary Maintenace has been carried out
3 BVN Buffalo of Hakubha Bachubha Gohil 29-07-08 FA Snapping of conductor AWAITED Not Applicable Not Applicable Awareness
4 BVN Mukeshbhai Shamjibhai Barad 29-08-08 NFHD due to breaking of DP pole AWAITED     Awareness
5 BVN Bogha Govind Baraiya 04-10-08 FHO Due to lekage of current from broken LT conductor AWAITED Not Applicable Not Applicable Necessary Maintenace has been carried out
6 BVN Shri Shankarbhai Fatehsinh  31-10-08 NFHO Due to electric Shock AWAITED Not Applicable Not Applicable Rectified Location
7 BVN  Shri Arjunbhai Ramanbhai Baraiya 31-10-08 NFHO Due to electric Shock AWAITED Not Applicable Not Applicable Rectified Location
8 BVN Shri Vipulbhai Chitarbhai Chudasama 04-09-08 FHO As per details given by victim’s father & other villagers that shri Vipulbhai Chitharbhai Chudasama was coming back to home at 19:30 ( approx.) in Ambali sheri village Ghanghali he came in contact with broken guy & got electric shock & met with fatal accident. AWAITED     Awareness
9 BVN Cow of Shri Bhagvanbhai Kamabhai Rabari 30-09-08 FA LT line phase conductor snapped & fell on road at Harijanvas. The cow passing nearby came in contact with this live LT conductor & got shock & died. AWAITED     Necessary Maintenace has been carried out
10 BVN Cow of Naranbhai Rambhai 13-11-08 FA Due to snapping of conductor AWAITED     Awareness
11 BVN Bullock of Mohanbhai Ranchhodbhai Vaghasiya 03-10-08 FA Electrocution & Falling Down From Pole AWAITED     Awareness
12 BVN Buffalo of Shri Ghelabhai Devshibhai Chauhan 04-10-08 FA Phase conductor of LT line of vill. Bajud snapped & a bullock passing under the LT line came in contact with the live conductor & got shock & died.  AWAITED     Awareness
13 BVN Shri Ghelabhai Devshibhai Chauhan 04-10-08 FA Phase conductor of LT line of vill. Paldi snapped & a Buffalo passing under the LT line came in contact with the live conductor & got shock & died.  AWAITED     Awareness
14 BVN Smt. Kajalben Jivanbhai Gohil 19-11-08 NFHO insulation failure on load side wire & victim touch with it. Accident occurred on private primises AWAITED     Awareness
15 BVN Shri Bakulbhai Bhagvanbhai Joshi 24-11-08 NFHD Mechanical accident AWAITED     Awareness
16 BVN Bhaveshkumar Hiteshbhai 27-12-08 FHO Snapping of Conductor AWAITED Not Applicable Not Applicable Maintenance Carried Out
17 BVN Shri Manishsinh Aandhubha Gohil 19/01/09 NFHD Slept down while climbing girder pole-Mechanical accident AWAITED     Maintenance Carried Out
18 BVN JIGNESH S VANZA 16.1.09 NFHD Mechanical accident AWAITED     Awareness
19 BVN Shri Jilubha Bhurabha Gohil 04.03.09 NFHD Mechanical accident AWAITED     Maintenance Carried Out
20 BVN Harpalsigh Babubha Sarvaiya 10.3.09 FHO A Man went for filling the water on terrace of Govt. Hospital Billding and water pipe chane one place to another place Due to sleep of his foot fall on and water came in contect with overhead 11kv line Hence,current was past through his body and electrodied his body and died AWAITED     MAITENANCE CARRIED  OUT
21 BVN Dhanjibhai Bachubhai Viradiya 17/03/09 FHO Victim was died due to came in contact with fencing on which broken LT line conductor was fall and victim got electric shock AWAITED     Maintenance Carried Out
1 AMR Fatal accident to Hunam outsider Late Dilipbhai Babubhai Mina age 35 approx at Kodinar city time 10:50 Am 25.10.08 FHO victim climb upon the bonat of the truck, which was stand under the 11 kv somnath Urban category feeder. Accidentally, victim came in contact with the live 11 KV conductor and met with fatal accident not recd      
2 AMR fatal accident to buffallo of Shri Dulabhai Govindbhai Mori at villae Barda, of kodinar city area. 24.10.08 FA due to snapping of LT conductor of Ag t/c. not recd     necessary maintainace work carried out
3 AMR Non fatal accident to DePT PERSON SHRI J. M. Trevedi Helper (VS) AT Village Toda, under Lathi Taluka 16.10.08 NFHD victim while attending the fault of burnt 11 kv DO jumper of load side of said transformer, accidently alluinium binding wire is touched with upper part of DO fuse which was live with 11 kv Power, as the said power was not shut off by the employe. recd The DyCEI suggested for utilization of safety gadjets as well as necessary precations for line clear yes the suggested remedies are sell conveyed in the field offices and discussed during safety meetings
4 AMR fatal accident to Human outsider late shri Balubhai Pithabhai Vadher and two nos of Buffalloes and one no of Cow of Shri Babubhai Devayatbhai Balai at village Mitiyaz taluka: Kodinar 1.11.08 FHO At approx. 7:00Am 11 Kv Mitiyaz Ag feeder was tripped and it was charged from 66 KV kodinar S/s and it stood charged OK. At about 7:35 am A cow and two nos of buffalloes came in contact with live 11 kv snapped conductor of said 11 kv Ag mitiyaz feeder. A person who is trying to away the conductor accidently came in contact with it and met with a fatal accident. not recd      
5 AMR FA not recd    
6 AMR FA not recd    
7 AMR FA not recd    
8 AMR fatal accident to Human outsider late shri Kanubhai Nanubhai Bhil at village Kana Talav taluka: Savarkundla. 8.11.08 FHO victim working on 3-pole DP structure for stringing of Disc cable wire while doing the said work accidently touched to live 11 kv conductor and met with a fatal accident recd The DyCEI stated that the victim himself was responsible for the accident yes such precaution is videly published in safety awareness program
9 AMR Non fatal accident to outsider Human Shri Laxmansinh Mangulsing Gelot age 20 yrs at village Khakhariya 4.12.08 NFHO Victim was doing jumper on 11 kv line on the down side of D.O.(Load side) and the D.O.wire touches the live 11 kv wire and get shock as the line was not shut off by any employee not recd     victim himself was responsible, necessary instruction given to the contractor for safe work
10 AMR Fatal accident to Buffallow of sh.Laxman Lavji at village Rampur 19-12-08 FA Snapping of conductor not recd     Maintainance work carried out 
11 AMR Non fatal accident (Mechanical) to Department person shri Suresh A. Bagda-Helper at village: Sarambhda, Taluka: Amreli 16.01.09 NFHD Victim while attending the consumer complaint fault on LT pole, while climbing the LT pole he slipped from the pole at about half of the height of the pole and met with MECHANICAL accident. not recd     said incident occurred during climbing the pole and victim slipped.
12 AMR Non fatal accident (Mechanical) to outsider person Shri Ghansyam Bhagvanbhai Vasani, employee of Nagarpalika at Chalala, Taluka: Dhari 28.01.09 NFHO Victim is employee of the Nagarpalika.He was doing streetlight repairing work. He was replacing the old street light conductor by new coated conductor.he has complated the jumpering work on previous LT pole than after doing work on end pole to stringing coated conductor.At that time due to tention on end pole, that LT pole broken down.and mechanical accident occured.   not recd     said incident due to showing negligency in work.
13 AMR Non fatal accident to outsider person Shri Satnamsing Jigarsinh 30 yrs approx. at Kodinar, Taluka: Kodinar  29.01.09 NFHO The Construction work was going on at Khodiyar mandir road in kodinar city so half of the road was blocked for traffic ,A Container Driver parked his Vechile about 15 feet far from the road , where  11 KV HT line was passed above this container .Because the container was more about 15 feet in hight so the Driver effected with the induction of this line . Driver name shri satnamsing jigarsing age 30 years was refferd to junagadh  by the local hospital (Ranawala Hospital ,Veraval road, kodinar) authority of kodinar .Information about this accident is received today by our line staff shri m.c. naqvi not by any complain or any other source not recd     Victim accidently came in contact with live line through the vehicle.
14 AMR Non fatal (Mechanical) accident to Deptt person Shri H.V.Helaiya lineman at village Amreli  8.02.09 NFHD Victim while climbing down from the girder pole  after completing the disconnection activity due to imbalancing of his body, he slipped from the pole. not recd     accidently victim loosing his balance while climbing down the pole necessary instruction given for safe work in future.
15 AMR Fatal accident to bullock, owner Shri Ayubhai Jamalbhai Chavda village Naliya Mandvi, Taluka: Una  13.02.09 FA due to snapping of conductor of 11 KV Div feeder. not recd     Maintainance work carried out 
16 AMR Non fatal accident to Human outsider Shri Balabhai Rambhai at village: Rajula city Taluka: Rajual 12.03.09 NFHO While victim passing under the line, a conductor of 11 KV line was snapped and layed on the jumper of R-phase disc insulaor. Hence vertical distance i.e. ground clearance between the line reduce, and victim accidently came in contact with live line and met with non-fatal accident. not recd     NA
17 AMR Non-fatal accident to departmental person (Mechanical) Shri Bhupatbhai Makwana at village: Bhingrad Taluka: Lathi 13.03.09 NFHD while victim climbing down the pole and accidently slipped down from the girder pole at about 13 to 15 feet height. not recd     NA
18 AMR Non-fatal accident to departmental person Shri Darshankumar Ravisankar Joshi- V.S.Helper - age 25  yrs, at village: Garmali Taluka: Chalala. 22.03.09 NFHD victim while carried out the maintainance work for LT line and also at place of work there is a crossing of 11 KV line. At that time another person who was cutting the tree and creepers any how accidently LT conductor touched the live 11 line and due to momentarily experience the 11 KV power, and met with non-fatal accident. not recd      
19 AMR Fatal accident to Human outsider Shri Panchabhai Kadvabhai Chavda-age 50yrs and non fatal accident to Smt. Daiben Panchabhai Chavda age-45yrs at village Oliya, Taluka: Savarkundla. 29.03.09 FHO fencing was made between the two farm by using metal wire clubbing the LT pole and its earthing wire. Y-phase conductor of lt line skipped from the shackle insulator and live power flow through earthing wire towards the fencing wire. Victims came in contact with fencing wire. not recd     Maintainance work carried out 
20 AMR NFHO not recd    
1 SNR Sh Mansukhbhai Bhagwanbhai Patel at vill Khodu 04/10/2008 FHO Victim got Ele shock in flat cable joint of submirsible pump at his farm- Internal wiring. AWAITED AWAITED      
2 SNR HNF: Sh Jitendra Amrutlal Yadav at vill D'dhra 24/10/2008 NFHO Both victims got ele shock while they were working on private LT Line of MES in militry area. They were MES's contractor's labours. AWAITED AWAITED      
3 SNR HF: Sh Hareshkumar Rameshwarlal Pandit 24/10/2008 FHO Both victims got ele shock while they were working on private LT Line of MES in militry area. They were MES's contractor's labours. AWAITED AWAITED      
4 SNR Sh Natubhai Virambhai Khachar At vill Umarda 15/11/2008 FHO Un-authorised work on TC centre. Victim removed two nos DO and tried to attend the HT jumper and got electrical accident. AWAITED AWAITED    
5 SNR Sh Bhimjibhai Khodabhai Sapra At vill Manadasar 30/11/2008 FHO Conductor Snapping of 11 KV Vijaliya Ag feeder due to pin puncture AWAITED AWAITED   conductor replace & maintenance
6 SNR COW of Sh Bhikhabhai Govindbhai Bharwad at vill LIMBDI 01/12/2008 FA Leakage of Earthing AWAITED AWAITED   Leakage removed&Earthing reactivated 
7 SNR COW of Sh Gokalbhai Polabhai Dharajiya at vill LAKHTAR 05/12/2008 FA Leakage of Earthing AWAITED AWAITED   Leakage removed&Earthing reactivated 
8 SNR COW of Sh Dhirubhai Khimabhai Dangar at vill Mayurnagar 08/12/2008 FA Snapping of conductor AWAITED AWAITED   conductor replace & maintenance
9 SNR FA to Sh Becharbhai Hemubhai Detroja at vill Bhalgamda 19/12/2008 FHO Snapping of conductor AWAITED AWAITED   conductor replace & maintenance
10 SNR FA to Amrutbhai Shankarbhai Chauhan Contracto's Labour at vill Chachka 20/12/2008 FHO During Stringing conductor of Ag conn, conductor came in induction zone of nearby JGY feeder &victim met with accident. AWAITED AWAITED   SHOWCAUSE NOTICE ISSUED.
11 SNR FH to Maheshbhai at S'nagar 10/02/2009 FHO INTERNAL WIRING AWAITED AWAITED    
12 SNR FH to Bachubhai Sunkabhai at Vill Dungarpur 13/02/2009 FHO INTERNAL WIRING AWAITED AWAITED    
13 SNR FH to Kailashben Vahanbhai at Vill Palasha 03/03/2009 FHO LT conductor Snapping AWAITED AWAITED   conductor replace & maintenance
14 SNR Bufflow of Harikushanbhai Bhanjibhai At vill. Pratapgadh 07/03/2009 FA LeAKAGE OF HT power through stay AWAITED AWAITED   Stay tighten